Produced daily, the Morning Report provides the ISO's best estimate of expected capacity available to meet peak-hour electricity demand and reserve requirements - key parameters used to operate the power system reliably.
For the weekly forecast, see the Seven-Day Capacity Forecast.
View the Morning Report below or Download a CSV file. Hover over items for an explanation.
Morning Report
Today's Information
3. Operable Capacity Analysis |
(MW) |
A. Capacity Supply Obligation (CSO)
|
28,343 |
B. Capacity Additions EcoMax Bid > CSO
|
1,660 |
C. Generation Outages and Reductions
|
6,788 |
D. Uncommitted Available Generation (non-fast-start)
|
6,941 |
E. DRR Capacity
|
246 |
F. Uncommitted Available DRR
|
12 |
G. Capacity Deliveries: Net Purchases = (-) Net Sales = (+)
|
|
|
Highgate |
0 |
|
|
NB |
-85 |
|
|
NYISO AC |
-562 |
|
|
NYISO CSC |
140 |
|
|
NYISO NNC |
-25 |
|
|
Phase 2 |
-309 |
|
|
Net Deliveries
|
|
-841 |
H. Total Available Capacity (A+B-C-D+E-F-G)
|
17,349 |
I. Peak Load Forecast For Hour Ending 20
|
13,000 |
J. Total Operating Reserve Requirement
|
2,122 |
K. Capacity Required = I+J
|
15,122 |
L. Surplus = (+) Deficiency = (-) (H - K)
|
2,227 |
M. Replacement Reserve Requirement
|
160 |
N. Excess Commitment Surplus = (+) Deficiency = (-) (L - M)
|
2,067 |
4. Largest First Contingency |
(MW) |
____ |
1,250 |
8. Weather Forecast Summary for the Peak Hour
|
CITY |
CONDITIONS |
WIND |
HIGH TEMP (°F) |
Boston
|
Cloudy |
E-12 |
52 |
Hartford
|
Rain |
E-9 |
63 |
11. Units Committed to Meet Minimum Operating Reserve and Replacement Reserve Requirements
|
(MW) |
0 Units
|
0 |
Report Generated 05/09/2024 07:55 EDT
Download a CSV file of this Morning Report
.