Produced daily, the Morning Report provides the ISO's best estimate of expected capacity available to meet peak-hour electricity demand and reserve requirements - key parameters used to operate the power system reliably.
For the weekly forecast, see the Seven-Day Capacity Forecast.
View the Morning Report below or Download a CSV file. Hover over items for an explanation.
Morning Report
Today's Information
3. Operable Capacity Analysis |
(MW) |
A. Capacity Supply Obligation (CSO) |
29,591 |
B. Capacity Additions EcoMax Bid > CSO |
1,433 |
C. Generation Outages and Reductions |
7,590 |
D. Uncommitted Available Generation (non-fast-start) |
7,553 |
E. DRR Capacity |
315 |
F. Uncommitted Available DRR |
12 |
G. Capacity Deliveries: Net Purchases = (-) Net Sales = (+) |
|
|
Highgate |
0 |
|
|
NB |
-53 |
|
|
NYISO AC |
-251 |
|
|
NYISO CSC |
50 |
|
|
NYISO NNC |
90 |
|
|
Phase 2 |
-1,320 |
|
|
Net Deliveries |
|
-1,484 |
H. Total Available Capacity (A+B-C-D+E-F-G) |
17,668 |
I. Peak Load Forecast For Hour Ending 21 |
13,500 |
J. Total Operating Reserve Requirement |
2,208 |
K. Capacity Required = I+J |
15,708 |
L. Surplus = (+) Deficiency = (-) (H - K) |
1,960 |
M. Replacement Reserve Requirement |
160 |
N. Excess Commitment Surplus = (+) Deficiency = (-) (L - M) |
1,800 |
4. Largest First Contingency |
(MW) |
____ |
1,320 |
8. Weather Forecast Summary for the Peak Hour |
CITY |
CONDITIONS |
WIND |
HIGH TEMP
(°F) |
Boston |
Mostly Clear |
S-10 |
60 |
Hartford |
Mostly Clear |
S-11 |
62 |
11. Units Committed to Meet Minimum Operating Reserve and Replacement Reserve Requirements |
(MW) |
0 Units |
0 |
Report Generated 05/26/2022 07:38 EDT