Produced daily, the Morning Report provides the ISO's best estimate of expected capacity available to meet peak-hour electricity demand and reserve requirements - key parameters used to operate the power system reliably.
For the weekly forecast, see the Seven-Day Capacity Forecast.
View the Morning Report below or Download a CSV file. Hover over items for an explanation.
Preliminary Morning Report
Today's Information
3. Operable Capacity Analysis |
(MW) |
A. Capacity Supply Obligation (CSO)
|
28,492 |
B. Capacity Additions EcoMax Bid > CSO
|
2,253 |
C. Generation Outages and Reductions
|
2,226 |
D. Uncommitted Available Generation (non-fast-start)
|
10,692 |
E. DRR Capacity
|
230 |
F. Uncommitted Available DRR
|
12 |
G. Capacity Deliveries: Net Purchases = (-) Net Sales = (+)
|
|
|
Highgate |
-161 |
|
|
NB |
-392 |
|
|
NYISO AC |
193 |
|
|
NYISO CSC |
205 |
|
|
NYISO NNC |
146 |
|
|
Phase 2 |
-896 |
|
|
Net Deliveries
|
|
-905 |
H. Total Available Capacity (A+B-C-D+E-F-G)
|
18,950 |
I. Peak Load Forecast For Hour Ending 20
|
14,860 |
J. Total Operating Reserve Requirement
|
2,546 |
K. Capacity Required = I+J
|
17,406 |
L. Surplus = (+) Deficiency = (-) (H - K)
|
1,544 |
M. Replacement Reserve Requirement
|
160 |
N. Excess Commitment Surplus = (+) Deficiency = (-) (L - M)
|
1,384 |
4. Largest First Contingency |
(MW) |
____ |
1,602 |
8. Weather Forecast Summary for the Peak Hour
|
CITY |
CONDITIONS |
WIND |
HIGH TEMP (°F) |
Boston
|
Mostly Cloudy |
W-11 |
40 |
Hartford
|
Mostly Cloudy |
SW-7 |
40 |
11. Units Committed to Meet Minimum Operating Reserve and Replacement Reserve Requirements
|
(MW) |
0 Units
|
0 |
Report Generated 03/19/2024 03:06 EDT