Produced daily, the Morning Report provides the ISO's best estimate of expected capacity available to meet peak-hour electricity demand and reserve requirements - key parameters used to operate the power system reliably.
For the weekly forecast, see the Seven-Day Capacity Forecast.
View the Morning Report below or Download a CSV file. Hover over items for an explanation.
Morning Report
Today's Information
3. Operable Capacity Analysis |
(MW) |
A. Capacity Supply Obligation (CSO)
|
27,846 |
B. Capacity Additions EcoMax Bid > CSO
|
1,876 |
C. Generation Outages and Reductions
|
1,381 |
D. Uncommitted Available Generation (non-fast-start)
|
10,187 |
E. DRR Capacity
|
243 |
F. Uncommitted Available DRR
|
12 |
G. Capacity Deliveries: Net Purchases = (-) Net Sales = (+)
|
|
|
Highgate |
-225 |
|
|
NB |
-514 |
|
|
NYISO AC |
-1,426 |
|
|
NYISO CSC |
150 |
|
|
NYISO NNC |
100 |
|
|
Phase 2 |
-1,807 |
|
|
Net Deliveries
|
|
-3,722 |
H. Total Available Capacity (A+B-C-D+E-F-G)
|
22,107 |
I. Peak Load Forecast For Hour Ending 18
|
18,870 |
J. Total Operating Reserve Requirement
|
2,792 |
K. Capacity Required = I+J
|
21,662 |
L. Surplus = (+) Deficiency = (-) (H - K)
|
445 |
M. Replacement Reserve Requirement
|
180 |
N. Excess Commitment Surplus = (+) Deficiency = (-) (L - M)
|
265 |
4. Largest First Contingency |
(MW) |
____ |
1,807 |
8. Weather Forecast Summary for the Peak Hour
|
CITY |
CONDITIONS |
WIND |
HIGH TEMP (°F) |
Boston
|
Clear |
NW-14 |
27 |
Hartford
|
Clear |
NW-11 |
26 |
11. Units Committed to Meet Minimum Operating Reserve and Replacement Reserve Requirements
|
(MW) |
1 Units
|
336 |
Report Generated 01/15/2025 12:00 EST
Download a CSV file of this Morning Report
.